PowerSense PQM 1000

pqm pic

Aimed at the "first level" of mains analysis, the PQM-1000 is an easy to use, low cost mains monitor, designed to fit into any tool kit or briefcase. Whether used for pre-installation mains investigations or fault finding, it provides accurate information on the quality of any single phase supply.

The main features of the PQM-1000 are as follows:

  • All types of AC mains disturbances monitored.

  • Power Failures (Blackouts)

  • Voltage Drops (Sags)

  • Low Line Voltages (Brownouts)

  • Voltage Surges (Surges)

  • High Line Voltages (Over Voltages)

  • Voltage Spikes L-E & N-E (Impulses)

  • High Frequency Noise L-E & N-E (Impulses)

  • HighlLow Line Frequency

Total of 15 Pre-set thresholds - no programming required.

LED indicators to show occurrence of past or present disturbances.

Two line Liquid Crystal Display (LCD) provides "real-time" display of Line Voltage and Line Frequency, High Frequency Noise (L-E & N-E), and the Disturbance Event Counts.

Simple operation using only 2 keys enables, scroll up or down through the different displays and event counts, and the event count memory to be cleared.

Powered directly from the monitored supply, no special connections are necessary.

Battery backed memory holds data during prolonged power failures.

Dimensions: 196H X 100W X 40D (mm) Weight: 550gms.

Optional Extras: Carrying Case.

SPECIFICATIONS

PQM-1000 Preset Thresholds - for each of the 15 event counts, for 50Hz mains supplies, along with the associated LED indicator.

Nominal Supply Voltage

220v

230v

240v

Duration

LED - Power Failure

<155v

161v

165v

>5.0 cycles

LED - Volt Drop

<187v

196v

216v

>0.5 cycles

LED - Low Line

<198v

207v

226v

>5.0 cycles

LED -Volt Surge

>253v

265v

264v

>5.0 cycles

LED - High Line

>243v

253v

255v

>5.0 cycles

Present voltages comply with most electrical supply companies contracted levels for each nominal line voltage.

120v - 60Hz Version is also available.


The following thresholds are common to all voltage ranges.

LED - Spikes

L-E >150 Volts Spike
L-E >300 Volts Spike
N-E >150 Volts Spike
N-E >300 Volts Spike

LED - HF Noise

L-E HFN >5.0 Volts p-p for 10mSec.
L-E HFN >15.0 Volts p-p for 10mSec.
N-E HFN >5.0 Volts p-p for 10mSec.
N-E HFN >15.0 Volts p-p for 10mSec.

LED - Frequency

>50.5 Hz for 4 seconds (High Frequency)
<49.5 Hz for 4 seconds (Low Frequency)

Distributed by:

POWERSENSE TECHNOLOGY LTD.

Unit 3, Morley Business Centre
Morley Road
TONBRIDGE
Kent
TN9 1RA
Telephone: 01732 771818
Fax: 01732 771881